Multifunctional electroprobe – DB

DB-elektroszonda

The DB Electroprobe is intended for use in the sector of level control instruments, opens up a whole new field of multifunctional equipment.

Application: in the field of level control instruments, it is a multifunctional device.
Advantages: an extremely innovative product which unites a series of
functions in a very small space (4 DIN modules):
ON-OFF electroprobe (operating in one single point): acts on relay 2 using probes
6 and 12.
– Differential electroprobe (operates between two probes positioned by installer): acts
on relay 1 using probes 10 and 11, always together with 6 and/or 7 as common.
– High alarm: use probes 9 and 6.
– Low alarm: use probes 8 and 7.
– Internal Buzzer: For high and low alarms.
– Control for external alarm (buzzer or light).
Benefits: Possibility of activating or deactivating controls by means of dipswitch. The
installation of 4 electroprobes would be necessary to obtain the same functions.

Power supply 24 V~ – 117 V~ 230 V~ 50 ÷ 60 Hz
Inter electrode voltages 24 V~
Consumption Max 10 VA
Operating resistance 0 – 20 KΩ
Relase resistance  > 20 KΩ
Mounting on DIN rail
Contact rating 5(2)A 250V
Contact rating alarm relay AC1 0,5A 250 V ~ resistive
Response time 100 ms
Operating temperature – 10°C ÷ + 50 °C
Storage temperature – 20°C ÷ + 80 °C
Housing box Noryl (PPO) UL 94 V0
Protection rating IP20
Approval CE
Dimensions 90x72x60 mm
Weight 320 gr.
Max cable leght of probes 20 meter